Non Fire Rated Buildings and Boundaries
- A non-fire rated boundary is less than 30 minutes fire protection.
- A non-fire rated boundary is defined as a fence, wall, hedge or vegetation.
- A non-fire rated boundary must be 760mm away from the oil tank.
- A non-fire rated building must be 1.8 meters away from the oil tank.
- Any screening, including trellis, plants and foliage used to screen the oil tank must be 600mm away from the oil tank.
Fire Rated Buildings and Boundaries
- A fire rated building and boundary is more than 30 minutes fire protection.
- A fire rated building and boundary is defined as being without openings within 1.8 meters of the oil tank.
- Fire rated boundaries must extend 300mm at both ends of the oil tank and 300mm above for the whole length of the oil tank.
Building Eaves and Flue Terminals
- Eaves of a building must be 1.8 meters away from the oil tank.
- Eaves less than 1.8 meters away from the oil tank require fire protection.
- Flue terminals must be 1.8 meters away from the oil tank.
Oil Tank Base and Platform
- A fire rated ground base must extend 300mm on all sides of the oil tank.
- A fire rated platform must extend 100mm on all sides of the oil tank
(In conjunction with a 300mm fire rated ground base)
- If no fire rated ground base is provided, a fire rated platform must Extend 300mm on all sides of the oil tank.
Visit us at HSNW | HSNW Oil | HSNW Gas | HSNW Plumbing | HSNW Oil Tanks
Home Tanks Installation Tank Quote Gauges and Alarms Boiler Service FAQ Testimonials Contact
|
Book your Boiler Service online Receive 5% Discount* |
| Boiler Breakdowns Your Heating and Plumbing Repairs and Emergencies
|
| Oil Tank Quote Fill in our online form and receive your quote
|
| Ask a Question? Just give us a call or click here
|
| Quote invoice number ![]() |
Division of Heating Solutions NW